 | Nanotech 2007 Vol. 4
Technical Proceedings of the 2007 NSTI Nanotechnology Conference and Trade Show, Volume 4
Chapter 6: Cleantech: Emissions, and Environmental |
| | Study on non-Freon air cooling system using water refrigerant | | Authors: | A. Sugawara, S. Nakamikawa, M. Kageyama, S. Yamazaki, N. Abe, T. Itou, A. Tsurumaki and K. Kawasaki | | Affilation: | Niigata University, JP | | Pages: | 652 - 655 | | Keywords: | Air Cooling System, Water, Vacuum pump, Temperature, COP | | Abstract: | This paper aims for construction of a small, clean air cooling system using a water refrigerant and examines it experimentally. We offer a basic report for realization of the non-Freon air-cooling system using only water as a refrigerant. An experimental device consists of two groups, the first stage is composed a vacuum pump and a vacuum container of about 60 liters in volume, and the second stage has two heat exchangers (the one is heat load) and a water circulation pumps. The temperature characteristics of each place are measured by thermocouples. An air-conditioner indoor unit or a heater for as heat load was used; the air conditioning measurement and the energy were measured, respectively. Consequently, in air-cooling system used only water refrigerant, the ability to cool a room air enough was provided. The development of a new vacuum pump which can exhaust a large amount of water vapor is introduced as an appendix. | | ISBN: | 1-4200-6376-6 |
| Pages: | 768 |
| Hardcopy: | $199.99 |
| Order: | Mail/Fax Form |
| Special: | 3 CD Set — 15% off with Free Shipping |
| Up | |
|
| Upcoming Events |
 |
 |
 |
 |